Building automation

Points by AHU, VAV, fan-coil and chiller; schedule and override audit; simultaneous heating and cooling; set-point drift; trend-log quality. Back to Buildings and chillers · Data centres

2 units with a remaining-life estimate

Equipment tree

Click a check to see why an alarm would be raised, at your chosen level.

BMS points view

The points CAPMAC reads for each kind of equipment. All are read only.

AHU

PointBACnet object typeWhy it is read
Supply air temperatureanalogInputDischarge temperature after the coils
Mixed air temperatureanalogInputAfter the dampers, before the coils
Return and outdoor air temperatureanalogInputFor the free-cooling and damper reasoning
Outdoor-air damper positionanalogOutputCommand and, if wired, feedback
Heating valve and cooling valve positionanalogOutputBoth are needed to see simultaneous heating and cooling
Supply fan status and speedbinaryInput / analogOutputOn-off and speed
Static pressureanalogInputDuct pressure the fan holds
Occupancy schedule statebinaryValueWhich mode the BMS thinks it is in

VAV box

PointBACnet object typeWhy it is read
Zone temperatureanalogInputSpace reading
Zone set-point (cooling and heating)analogValueWatch for drift and overrides
Airflow reading and airflow set-pointanalogInput / analogValueNeeded for the bias and stuck-damper checks
Damper positionanalogOutputCommand
Reheat valve positionanalogOutputReheat running while the zone is warm is a waste
Discharge air temperatureanalogInputAfter reheat

Fan-coil unit

PointBACnet object typeWhy it is read
Zone temperature and set-pointanalogInput / analogValueSpace reading and target
Fan speed or statemultiStateOutput / binaryOutputLeft on out of hours
Heating and cooling valve positionanalogOutputValve against command
Supply and return water temperatureanalogInputWater-side fouling and valve leak

Chiller

PointBACnet object typeWhy it is read
Leaving and entering chilled-water temperatureanalogInputDelivered cooling
Leaving and entering condenser-water temperatureanalogInputHeat rejection
Compressor power or currentanalogInputEfficiency
Chilled-water flowanalogInputDuty
Status and alarm wordbinaryInputTrips and lockouts

Audits and reports

These look across your whole BMS. Evidence level on each says how far we have tested it.

Schedule and override audit Not yet tested: report only, no alarm claimed

Lists every point where the BMS is not following its own schedule: a fan or valve forced on, a set-point manually held, an occupancy mode stuck. Needs the schedule state and the override flags read read-only over BACnet.

Evidence The closest tested piece is the fan-coil left-on-out-of-hours check, caught in two held-out simulated tests. The audit as a whole has no test yet.

Simultaneous heating and cooling Simulated test: passed

Flags units whose heating and cooling valves are both open at the same time. Reads the two valve positions of each AHU, VAV and fan-coil.

Evidence Valve-leak checks for air handlers passed 8 of 8 and 6 of 6 on simulated records. A report of both valves open in your own data needs no test: it is a count of your own readings.

Setpoint drift Not yet tested: report only, no alarm claimed

Shows where a zone set-point has moved away from the commissioned value over weeks. Reads the set-point point each night.

Evidence No test yet. A plain count of changes, not an alarm.

Trend-log quality Real data: report only

Shows gaps, flat-lines, stuck values and spikes in the logs the BMS already keeps.

Evidence It stays a report you read yourself; it does not raise alarms.

Working checks

CheckEquipmentEvidence levelResult
VAV boxReal data: partly passedReal building: evening 18 of 18 passed; night 15 of 18 passed; morning 10 of 18 stopped on an older version.
VAV boxReal data: partly passedReal building: evening 7 of 8 passed; night 0 of 8 stopped; morning 1 of 8 stopped on an older version.
Fan-coil unitOutside simulator: passedTwo LBNL laboratory-unit files (outside simulator, not real plant data): severe fouling alarmed on 81 of 89 days. Heating-side fouling is not proven.
Fan-coil unitHeld-out test on simulated records: passedSix checks caught faults in two held-out tests.
Air handlerSimulated test: passedStuck damper 8 of 8, mixed-air bias 8 of 8, cooling-valve leak 8 of 8, heating-valve leak 6 of 6, 0 false in 17 records and 120 healthy days.
Air handlerReal data: partly passedReal Korean office air-handler data: injected bias found with no false call on a sham run; 9 of 19 stretches could be judged and natural faults could not be tested.
Cleanroom suiteSimulated test: passedDoor ajar between rooms 1 and 2 caught in 6 of 6 records, 0 false in 10.

Case studies

Real data first.

Real data from Figshare 27948192 (VAV building; Im, Jung, Yoon)
REAL DATA one building, fault-injected days

Stuck damper: evening 18 of 18 found, night 15 of 18 found. Airflow sensor bias: evening 7 of 8 found. 1 of 234 healthy boxes raised an alarm in the evening set.

Outside simulator: LBNL laboratory fan-coil files
OUTSIDE SIMULATOR two files, cooling water side; not real plant data

Severe fouling alarmed on 81 of 89 days. Heating-side fouling is not proven.

Real data from an office air handler (Korea, figshare 25909813) and an Iowa air handler (ASHRAE RP-1312 set, figshare 29297999, Ghalamsiah et al.)
REAL DATA injected bias; healthy quiet-only

Injected bias was found on a narrow test (9 of 19 stretches judged). The Iowa healthy air handler stayed quiet; fault detection could not be tested there.

Real data from the ASHRAE / Nesbitt air-handler set
REAL DATA figshare 29297999

A check built from the unit's own normal level found 1 of 2 damper days on a thin test. Small sample; trial on your own records recommended.

Held-out fan-coil tests on simulated records
HELD-OUT TEST, SIMULATED RECORDS simulated records

Valve leak, filter, sensor bias, stuck valve, fan loss and left-on-out-of-hours were caught in both fan-coil tests.

Building and chiller tests
SIMULATED TEST simulated records

Chiller evaporator fouling 6 of 6; air-handler damper 8 of 8; cleanroom door 6 of 6; 0 false alarms in the healthy records. Power for false-alarm evidence was thin (2 to 4 look-alikes per family).

What is not claimed yet

Connect

Connect

CAPMAC only reads. For a building automation system it can read BACnet/IP points through a read-only connector (optional extra, installed only when used). It never writes, overrides or releases a point. See the Connect page.

Remaining life: air handler and coil points