CRAH / CRAC units, the chilled-water loop, hot and cold aisles, supply air and the energy view. Back to Buildings and chillers · Building automation

2 units with a remaining-life estimate

Equipment tree

Click a check to see why an alarm would be raised, in your chosen level.

Air and water loop in one line

Rack heat → hot aisle → CRAH coil → chilled-water loop → chillers, towers or the free-cooling exchanger → outside. Supply air returns to the cold aisle. Each step has a reading we can watch.

Working checks

Evidence level is shown on every row. Each check says what is wrong now, and how sure we are from the test.

CheckEquipmentEvidence levelResult
CRAH / CRACHeld-out test on simulated records: passedNamed in 8 of 10 held-out tests of 12 faulted records each.
CRAH / CRAC coilHeld-out test on simulated records: passedNamed in 8 of 10 held-out tests; air side and water side are named as a pair, not told apart.
Containment, floor, blanking panelsHeld-out test on simulated records: passedBypass named; small recirculation leaks cannot be told apart from bypass.
CRAH valveHeld-out test on simulated records: passedNamed in 9 of 10 held-out tests.
CRAH fanHeld-out test on simulated records: passedNamed in 10 of 10 held-out tests.
CRAH fan driveHeld-out test on simulated records: passedNamed in the latest held-out tests (8 of 8 strong faults).
Supply plenum and ductsHeld-out test on simulated records: passedNamed in 10 of 10 held-out tests.
Plate heat exchanger / economiserHeld-out test on simulated records: passedNamed in 9 of 10 held-out tests.
ChillerSimulated test: passed6 of 6 in the building-chiller test; 0 false calls in 16 healthy and look-alike records.
Chiller condenserHeld-out test on simulated records: passed2 of 2 in the held-out plant test; 1 of 1 in the tower test.
Cooling towerHeld-out test on simulated records: passedHeld-out tower test passed on condenser tube fouling; tower pieces are covered by the plant checks.

Case studies

Real data first.

Real data from a data centre cooling plant
REAL DATA none yet

We do not have a real data-centre cooling data set to show. We are not filling this slot with simulated data. If you can share trends from one CRAH loop, the Connect page explains how we read them without writing anything back.

Real data from the FrostByte chiller rig (TH Wildau)
REAL DATA doi 10.15771/1894

The same chilled-water loop physics as a data-centre plant. On rig data it had not seen, all four marks passed: 12 of 12 severe fault groups named right and none of 8 healthy periods alarmed (lab rig, large faults only). FrostByte (TH Wildau), CC BY-NC 4.0 · shown one-to-one only; do not copy or forward · credit TH Wildau.

Held-out test: data-centre cooling, 10 tests
HELD-OUT TEST, SIMULATED RECORDS held-out test DC records (simulated)

8 of 10 tests passed every mark. Across the ten, 99 of 120 single faults were named after onset and 76 of 80 strong faults. 1 of 14 healthy records raised an alarm and 4 of 40 look-alikes did.

Open test, data-centre cooling
SIMULATED TEST simulated records

9 of 12 single faults named after onset, 0 of 3 healthy raised. Smaller faults (a supply-air rise of 1 K, a stuck-open economiser, a fan cap that never binds) are not claimed.

What is not claimed yet

Energy view: PUE-style

Type in the average power from your own meters over a period. Example numbers are filled in; replace them. This is a calculation on your numbers, not a prediction.

PUE-style ratio (total over IT)
Total power Cooling share of total

Free-cooling hours come from the heat exchanger in the equipment tree: when it fouls, the cooling line in this view rises on cool days. Read the two together.

Connect

Connect

CAPMAC only reads. For a building automation system it can read BACnet/IP points through a read-only connector (optional extra, installed only when used). It never writes, overrides or releases a point. See the Connect page.

Data-centre cooling plants usually expose the same points over BACnet/IP or OPC UA; both connectors are read-only.

Remaining life: data centre cooling and power

Faults this app caught, by equipment

Rows with a Replay button come from a recorded run with a named planted fault. Rows without one are checks that caught every planted fault in their scored tests.